Binding a property to a variable is the whole subscription. Point a field at a tag with $var, and the server subscribes on your behalf and streams updates to the screen. Writable tags flow the other way.

How the live pipeline works

Three hops, two protocols:

Hop Carried over
PLCs The server subscribes, writes and browses. OPC-UA
FastAPI server Holds the connection pool; fans values out to every screen. WebSocket
Operator screens Widgets re-render on each update to their tags. —

A browser only ever subscribes to the tags actually on screen. A viewport-aware fast / slow window refreshes visible tags first, so what the operator is looking at stays the freshest. Two things join that fast set regardless of what is on screen: alarm trigger tags and historized variables. The Admin area lists the whole set live — see Diagnostics.

Bind a property to a tag

  1. Select the widget and its field — e.g. a Label's Text. Click the field's source pill and choose Variable.
  2. Pick the tag from the tree — The variable picker shows your datasources' trees. Choose a leaf — say LinePLC:Motor1/Speed. For an array, choose one of its elements (Temps[2]) to bind that element for good, or the array itself. A field that takes one value accepts the whole array too — the picker marks it ✓ and says to choose the element in the field's Index row: confirming it adds an index box right under the variable, with a light Element of the array, 0 to 4 hint above it. Type the element's number there, or take it from another value with the row's source pill — a dialog's input, say, so one popup reads and writes Safety/Open[device] for whichever device opened it. Reads, Write Data Variable, Toggle Boolean Variable, Edit Value and an alarm's values all follow it; an index that is empty or past the end reads nothing and a write fails with array_index_out_of_bounds. The tree lists only tags that fit the field; Show all lists the rest to browse, but a tag marked ✗ cannot be confirmed — that includes a tag that is disabled in its datasource: enable it there first. Inside a source each slot lists what that slot takes — a condition or either side of a comparison any tag, a formula's {1} numbers and Booleans. One bit of a status word. Where a field takes a Boolean — an LED's Value, a toggle target, a formula's {1} — the picker shows a Bits checkbox. Tick it and every whole-number tag of 8, 16 or 32 bits (OPC-UA Byte, SByte, UInt16, Int16, UInt32, Int32, a static Integer) opens onto its bits: Bit 0, the lowest, up to Bit 15 for a 16-bit word. Pick one and the field shows it as Plant:Battery/Status.5. The bit reads as a Boolean and is written as one: the server reads the whole word fresh from the controller, sets or clears that one bit, and writes the word back. Should the controller change another bit of the same word in that moment, its change is lost — so let the HMI write only words the controller does not write itself. The bit of an array element cannot be picked. Alarms, recipes, the historian and a trend take whole tags only, so their pickers have no Bits box.
  3. Watch it go live — The canvas immediately reflects streamed values. That's the subscription — there's nothing else to register.
// a scalar tag
"value": { "$var": { "path": "LinePLC:Motor1/Speed" } }

// one element of an array
"value": { "$var": { "path": "LinePLC:Readings", "index": 0 } }

// a whole struct member reached by slash-path
"value": { "$var": { "path": "LinePLC:Motor1/Torque" } }

// bit 5 of a status word, read and written as a Boolean
"value": { "$var": { "path": "Plant:Battery/Status", "bit": 5 } }

The path is always datasource:location, with the location slash-separated. The prefix before the colon names the connection.

Write back to the machine

Mark a variable writable when browsing, and controls can push values to it. A Button binds a writable boolean — press it and the runtime sends a write_field message that sets the tag to true. A numeric setpoint written from a numpad works the same way. A variable not marked writable refuses every write — the server sends nothing to the machine and the operator sees Variable is read-only, whatever value was entered.

A single-precision tag — OPC-UA Float, which is an S7 Real or a CODESYS REAL — cannot hold most decimals exactly, so a write stores the nearest value it can, just as the PLC itself would: 48.2 is written as 48.20000076. A configured minimum or maximum is checked against the number entered, before that rounding, so a setpoint exactly on a bound is always accepted.

What happens when data goes bad

The runtime turns failure into a defined visual state — never a stale value passed off as live, and never a crash.

Situation Result
Absent Source can't produce a value yet (no matching index, a struct member that isn't there at runtime, a parameter with no value and no default) → the field uses its own fallback / placeholder.
Bad quality The tag is connected but reported bad / uncertain / stale → the field shows its quality-degraded state (blank or dimmed).
Disconnected The datasource itself is down → treated as bad quality for every tag it owns.

On/off widgets show Absent as a state of its own, so no value is never mistaken for off — and neither is an empty text or an invalid number from a tag. Until a bound value arrives (or when no variable is bound at all), an LED Indicator shows an empty ring instead of a grey lamp; a Switch shows a hollow track with its thumb midway and can't be pressed, since there is no state yet to invert; a Menu Toggle shows its collapsed icon dimmed in a dashed outline — pressing it still runs its actions but writes nothing until the state is known.

The marks on a widget

A widget whose bindings aren't delivering gets an overlay, and which one it is tells you where to look:

Mark Means Fix
Red — wrong binding The binding itself doesn't resolve: a tag that no longer exists, a member that isn't on the struct, an index past the end of the array, or a tag whose type doesn't fit the field. A configuration error — repair the binding.
Amber — no data The binding is sound, but no value has arrived. Look at the datasource, not the page — see Connect, disconnect, and see why it failed.
Dashed — disconnected The socket or the datasource is down, so every tag it owns is suspect. Connectivity. Cached values are never passed off as live here.

The amber mark waits for the server to say it has sent everything it is going to for this screen, so a value merely still in flight is never flagged. If that signal never comes — the backend is down — it appears anyway after a few seconds rather than hiding the problem. Dialogs are judged on their own delivery, not the page's, so opening one doesn't inherit a window that already closed.

Inside an $if or a $switch, only the branch on screen is judged. A tag in a branch that is not taken never marks the widget, so a value that is only shown in one state cannot flag the widget while the other state is showing.

A slow tag does not hold up the screen. A page reveals once its widgets' code has loaded — its variables are not part of that wait. A slow OPC-UA read shows up as an amber mark on the one widget waiting for it, instead of stalling the whole navigation.